Cause & Remedy

PROBLEM CAUSE REMEDY
LOWERING OF TEMPERATURE
DROP ACROSS COOLING
TOWER
FILLS CONDITION IS POOR REPLACE / CLEAN FILLS
FAN NOT IN OPERATION CHECK MOTOR, PUT FAN
IN OPERATION IN
CORRECT DIRECTION
DISTRIBUTION OF WATER THROUGH NOZZLES ON
FILLS NOT CORRECT
CLEAN THE NOZZLES
CHANGE IN DESIGN PARAMETERS AS WATER
FLOW RATE, AIR FLOW RATE
CHECK PUMP FLOW RATE, PLANT LOAD, CLEAN HEAT TRANSFER SURFACES WHEREVER POSSIBLE
ADJUST FAN BLADE ANGLE.
  WET BULB TEMPERATURE HIGHER CHECK DESIGN CONDITION, TRY TO AVOID SATURATED
AIR RECIRCULATION.
MOTOR NOT WORKING IMPROPER POWER SUPPLY CONSULT SUPPLY TERMINALS.
PHASE SUPPLY IMPROPER CHACK PHASE POWER, CONSULT POWER SUPPLY TERMINAL
STARTER NOT PERFORMING PROPERLY REPLACE STARTER,
CONNECT PHASE FAILURE SAFETY DEVICES.
MOTOR WINDING DAMAGED SEND OUT FOR REPAIR WITH SPECIFIC EXPLAINATION AS PER MOTOR QUALITY.
BEARING JAMMED CLEAN / REPLACE BEARING
FLUCTUATING WATER
FLOW OBSERVED
NOZZLES CLOGGED CLEAN NOZZLES
PUMP PERFORMING AT HIGHER/ LOWER DISCHRGE PRESSURE CHECK PUMP GRAPH, CHECK PUMP POWER, REMOVE AIR TRAP, REPLACE PUMP
SUMP WATER LEVEL LOW MAKEUP SUFFICIENT WATER IN BASIN
VALVES, PUMP BAFFELS, FILTERS CHOCKED PERFORM CLEANING ACTIVITY
WATER CARRY AWAY FROM
TOP OF TOWER
WATER FLOW MORE THAN DESIGH PARAMETER PUT THE CORRECT PUMP
NOZZLES CLOGGED, NOT IN POSITION CLEAN NOZZLES, PUT IN CORRECT DIRECTION
FILLS CHOCKED CLEAN / REPLACE FILLS 
MOTOR RPM HIGHER PUT THE CORRECT MOTOR WITH COMPARATIVELY
LOWER RPM
AIR FLOW NOT SUFFICIENT FILLS CLOGGED CLEAN / REPLACE FILLS
FAN ANGLE OF ATTACK
IN NOT CORRECT
INCREASE FAN ANGLE 
FAN SPEED NOT
CORRECT
CHECK MOTOR POWER SUPPLY VOLTAGE, BEARING CONDITION
EXCESS VIBERATION &
 NOISE THROUGH FAN
FAN NOT IN GOOD
CONDITION
REPLACE / REPAIR FAN
BALANCING NOT DONE DO STATIC & DYNAMIC BALANCING OF FAN
MOTOR NOT PERFORMING
IN GOOD CONDITION
CHECK MOTOR BEARING
MOTOR MOUNTING FRAME NOT IN GOOD CONDITION PUT A  GOOD MOTOR SUPPORT FRAME.
FAN TOUCHING CASING CREAT PROPER CLEARENCE BETWEEN FAN TIP AND CASING.

IN CASE OF ANY OTHER PROBLEM PLEASE  CONTACT US. 

 