|
The operating and maintenance instructions as
given below are of general nature.
1. PREPARATIONS FOR STARTING
1.1. Cleaning.
Open the drain plug of the cooling water tank and scrub the water
tank with a
brush to flow out the dirt.
1.2. Trial Circulation of Water.
Fill the water basin until the float valve cuts off. Start the
circulating pump
and make up the water level in the basin as necessary.
( Refer
also to pump
starting instruction-part 2.1 )
1.3. Checks.
After the circulations test, check for dirt or foreign matter
stuck to the
inside of the tower. Rotrate the fan by hand to check that it is
free and check
the fan blade tip clearance. Measure the supply voltage and check
that the power
supply suits the fan motor. Run the fan momentrarily to check the
direction of
rotation. It should rotate in anti clock wise direction. Then run
the fan for
two to three hours to check that no vibration or abnormal sound
develops.
Move the float of the float valve, up and down, to check its
discharge and
control of the water level.
Should the tower be idle for some months (either prior to
commissioning or due
to shut down ) the following extra checks should be made.
a) Check the insulation of the motor with a megger.
b) Check for loose nuts, especially at fan motor mountings and at
the
attachment of the casing and the tank.
2. STARTING
2.1. Pump Start Up
Run the Pump intermittently for 5 minutes to drive any air out of
the water
piping. Again check the water level in the basin before operating
the tower.
Start the pump, and adjust the necessary valves until the required
water flow
rate is obtained.
2.2. Fan Start Up
Check that there is no foreign matter near the air inlet and
outlet that could
interfere with the fan operation . After Starting the fan, check
the phase
currents and voltages to ensure that the motor is operating in
accordance with
name plate data.
3. OPERATIONAL CHECKS
3.1. Performance
The specified water flow must be maintained to obtain rated
cooling capacity. Be
sure that the tower interior is kept clean and that scale and
algae do not form.
3.2. Water Level
If the water level in the water basin drops, air may be drawn,
causing
cavitation in the pump. Hence, it is important to maintain the
water level.
3.3. Make regular checks for vibration and noise.
Also, regularly check the cooling water temperatures and the
electric current to
the fan. As the source of vibration or noise is usually the fan,
be careful not
to overlook even a slightest defect.
4. MAINTENANCE
4.1. Casing
No painting is needed for the casing as it is made of F.R.P. when
it is soiled,
wash it with soap and water.
4.2. Water Tank
Scrub the water tank when it is dirty. Flush any dirt out through
the drain.
4.3. Nozzles
Ensure that there is adequate water spray and the nozzles are not
blocked. If
nozzles are blocked remove them through the inspection window,
clean them and
refit them. Broken spray nozzles should be replaced.
4.4. Fill
PVC fills do not deteriorate and no attention is necessary
provided proper water
quality control is maintained. In case some scaling is observed
clean the fill
packs after removing them from the inspection / service window.
The fill packs
may be cleaned by a pressurized jet of water. If the scale is
still not removed
the packs may be cleaned by dipping them in dilute solution of HCL
acid
(Commercial grade).
4.5. Fan
Check and tighten Blade Clamping Hardware after about a week of
Commissioning
and at least at 6 monthly intervals thereafter visually inspect fan
every month
and clean the Blades if any dirt has accumulated on them. Dirt
accumulation on
Blades could affect balance and result in excessive vibration.
4.6. Fan Motor
Check fan motor bearings at best at 6 monthly intervals and
lubricate if
necessary.
5. PERFORMANCE
The performance of the Cooling Tower depends on – (a) water flow,
(b) water
temperatures inlet and outlet ), (c ) ambient wet bulb temperature
and (d)
air flow. A large temperature difference in the circulating water
does not
necessarily mean that the tower is of high performance. Similarly,
a small
temperature difference does not mean that it is of low
performance.
The temperature difference is small if the heat load is low. A
similar result is
seen when a large volume of water is flowing.
On the other hand, an higher heat load, a reduced water flow or
the higher water
inlet temperature makes the temperature difference larger. The
relevant factors
may be checked if the performance is not met.
6. CIRCULATING WATER MAKE UP
Loss of water from the Cooling Tower consists of evaporation and
carry over,
which is scattered about by the fan as drift. As continued
evaporation of the
circulating water results in increased hardness, corrosion of the
circulating
system is possible and scale may form. For this reason, blow-down,
in which part
of the circulating water is bled off, is necessary.
6.1. Evaporation Loss
Evaporation loss (E) can be calculated with the following equation
:

where
t : water temperature range deg.c
600 : latent heat of evaporation in kcal / kg
6.2. Carry over volume
It is very small in volume, and though it is affected by the
construction of the
tower proper to a certain extent, it is normally 0.2 to 0.3 % of
the volume of
the circulating water flow.
6.3. Blow-down volume
In order to drain part of the circulating water periodically or
continuously, it
is effective to leave the drain slightly open during operation, or
to let the
water overflow constantly by raising the operating water level or
to change the
water completely from time to time when the water basin is
cleaned.
The blow-down volume differs depending on the quality of the water
or the degree
of hardness. In most of the cases of air conditioning, about 0.3 %
blow-down is
usually necessary. For proper quantity of blow down, please send
the analysis
of make water, water circulation quantity and temperature range to
HIMGIRI so
that the desired blow down quantity can be informed to you. |